Description
Fire protection panel FS4000 is designed to work with conventional automatic fire detectors and manual call points. The panel has an output provided for external executive devices.
The device is produced in four versions:
2 fire alarm lines – FS4000/2
4 fire alarm lines – FS4000/4
6 fire protection lines – FS4000/6
8 fire alarm lines – FS4000/8
Technical characteristics
Fire alarm lines:
– Maximum number of fire detectors on the line: 32
– Connecting line: two-wire
– Maximum line resistance: 100 O
Current thresholds:
– Fault condition: 0 – 6 mA
– Working mode: 6 – 16 mA
– Fire condition: 16 – 80 mA
– Short circuit: > 80 mA
Results of fire condition monitoring:
– Quantity: 2 pieces
– Type: potential, relay with independent control
– Electrical characteristics: (19-27.5)V DC/1A
Relay output for fire condition:
– Quantity: 2 pieces
– Type: Potential-free, 1 switch, 1 NO
– Electrical characteristics: 3?/125V AC, 3A/30V DC
Relay output for fault condition:
– Quantity: 1 piece
– Type: potential-free, switching
– Electrical characteristics: 3?/125V AC, 3A/30V DC
Relay output for fault condition:
– Quantity: 1 piece
– Type: short-circuit activated non-monitoring type (potential-free contact)
– Electrical characteristics: 5 VDC in normal open state / 0 VDC in activation mode
Performance:
– Control of fire alarm lines and controlled output under fault conditions (short circuit and interruption) and automatic reset.
– Detection and automatic reset of the removed fire detector.
– Identification of manual call points.
– LED indicator for alarm and emergency.
– Delay in generating the fire condition for 1, 2, 3, 4, 5, 6 or 7 minutes after the fire condition is registered.
– Option of realization of two fire protection lines “logical and”.
– Duty Mode state with direct activation of fire condition stage 2 for two fire lines.
– Device status indication for data transmission RS485.
– RS485 communication interface enable/disable option.
– Built-in audio for fire condition – single tone, continuous, can be turned off.
– Built-in audio for defect condition – single tone, intermittent, can be turned off.
– Test mode for fire alarm lines.
– Disconnection of fire alarm lines.
– Disable output fire condition.
– Extension of parameters for additional relay output for fire condition for each line and built-in RS485 for local network operation.
– input for remote fire reset;
Displays of registered events:
– Lighting display: LED
– Sound: built-in buzzer
Power supply:
– Voltage: (100-240)V AC
– Frequency: 50/60 Hz
Backup batteries:
– Battery type: lead, gel electrolyte
– Number of batteries: 2 pcs
– Nominal voltage of backup battery: 12 V
– Nominal capacity C20: (7.0) Ah
– Charging voltage: 28V DC
Operation in Duty mode when the main power supply is interrupted:
Lines – 24V / 1.2Ah – 24V / 4.5Ah – 24V / 7.0Ah
2 lines – 32 hours – 120 hours – 180 hours
4 lines – 24 hours – 98 hours – 140 hours
6 lines – 20 h – 80 h – 110 h
8 lines – 16 h – 68 h – 90 h
Consumption of backup batteries:
– 2 line configuration: < 35 mA at 24V DC
– 4 line configuration: < 45 mA at 24V DC
– 6 line configuration: < 55 mA at 24V DC
– 8 line configuration: < 65 mA at 24V DC
Power source for external devices:
– Voltage: (19-27)V DC
– Maximum current value (including counter output current): 1.2A
fuses:
– main supply 230 V: 4.0 A
– Backup battery: 6.0 A
– Power supply for external devices: 1.85 A automatic
– Monitoring results: 1.1 Automatic
Size: 304mm x 222mm x 94mm
Weight (reserve batteries not included): 0.98 kg