Description
The optical smoke fire detector provides a reliable early warning of a fire condition that responds to a fixed threshold of smoke detected in the protected building.
The smoke sensitivity is factory set according to the European standard EN54-7.
The fire detector is controlled by a microprocessor. FD8030 works with an improved algorithm to self-compensate for optical camera contamination, indicating the need to clean the camera dust. It is done quickly due to the easy disassembly and assembly of the body cover.
The construction of the optical camera and the new technology used in the production of the screen provide a high level of protection against the penetration of dust particles and insects, and from working in conditions of strong air flow.
Technical data
Supply voltage: (10-30)VDC
Operating mode current: 120 μA
Fire protection condition
– Base type 8000 or 8000D: (8-25) mA
– Base type 8000R, 8000DR: (18-55) mA
Terminals: for wires with cross-section (0.8-2.5) mm2
Degree of protection: IP 43
Working temperature: from minus 10oC to 55oC
Relative humidity: (93±3) % at 40oC
Sensitivity: in accordance with EN54-7
Installation: Using 8000 series bases
Dimensions (base included): Ø100, h 47 mm
Casing material: ABS plastic, white
Weight (with base): 0.100 kg
Protected area: circle with a diameter of 15m, h 11m